PRODUCT
BH-N 3KVA/3KW HF Online 1/1 Phase Lithium-ion UPS
❤ Add to collection

BH-N 3KVA/3KW HF Online 1/1 Phase Lithium-ion UPS

Full DSP Controlled HF Online UPS

0.00
$0.00
$0.00
$0.00
Weight:0.00KG
Quantity:
(Inventory: 99999)
Buy now
Add to cart
Description

Full DSP Controlled HF Online UPS


1System Introduction 

BH-N Series Lithium-ion UPS system is a full DSP controlled, Adopt 3 level technology, online double conversion, 1/1 Phase pure sine wave online UPS,with smart design and high reliability, this series combined  the Lithium-ion battery with UPS control, charging, telecom into a whole system. overall efficiency95% BH-N series can be defined as a high reliability and energy saving green power.

 

2System Features

2.1High Performance Index

 Latest HF switching power supply rectifier and PFC Technology. Input Power Factor 0.99, THDI≤3%online single phase with double conversion structure, compatible with 208/220/230/240Vac50/60Hz Grid supply system.

 Wide Input Range from 110-300Vac in 100% loadIf Load is below 50%, it can be reached even equal or lower than 110Vac which can reduce the battery usage time and maximum the battery life span.

 Adopt Latest 3 Lever technology to meet the critical loads, with output PF =overall efficiency up to 95% (98.5% under ECO mode), BH-V is a energy saving green power.

 Powerful overload ability with output short circuit protection technology: 1-3 KVA: 120% overloads for 1 minute.150% for 60ms

transfer to bypass and alarm.

   6-10KVA: Utility mode: 102-110%:30 minutes, 110-130% :10 minutes, 130-150%:30s,  ≥150%:500ms

   6-10KVA: Battery mode: 102-110% :10 minutes, 110-130% :1 minute,  130-150% : 10s,  ≥150% 500ms

 Can be connected with all kinds of generators to save customers costs. 

 Intelligent charger systemcharging current from1-12A adjustableadopt constant charging, float charging and equalized charging methods , which could meets various requirements from different Lithium-ion battery pack and greatly expand batteries life time

 Powerful battery anti-reverse connected alarm and protection, if battery unconnected, UPS will alarm with DC unconnected, if the DC reversely connected due to the intention of installation personnel, UPS cannot turn on and shows DC failure, only when the DC connect well UPS will be work in normal.

 Powerful battery test function, users can do or cancel the battery test on LCD screen directly, this could greatly avoid UPS shutdown when the battery voltage is too low. Also solved the traditional battery test dilemma that engineer has  wait in site for the battery testing

 Intelligent recognition for short circuit, if the short circuit lasts less than 3s, UPS will restart to inverter mode automatically, if the short circuit lasts over 3s, UPS will lock the inverter with long time alarm.

 Under emergency status, the UPS output could be remote controlled under EPO mode 

 2.4 inch Large Color Dot-matrix LCD+LED Screen with multi-functional keyboard to check UPS and lithium-ion system parameters, such as work status, temperature control and fault histories, self-diagnosis periodically discharge settings, etc.

 Multi-page history record can be tracked on LCD highly improved the efficiency for site engineers to check the UPS and lithium-ion battery running days and cumulative running status of UPS

 Intelligent mute control technology and scientific ventilation design greatly reduce the UPS running noise

 Standard 19” Rack-mount design, compared to traditional VRLA battery pack, this Lithium-ion UPS system can be compatible with standard communication cabinet  and greatly save data room space

 Highly integrated PCBA board and wires design makes the system convenient in maintenance and greatly saves after-sale time.

3Competitive points

◆ Fully DSP control online UPS which provide outstanding stability and reliability

 Output PF=1.0overall efficiency above 95%

 Intelligent battery management, UPS charging current can be adjustable from 1-12A

 Powerful overload ability with output short circuit protection technology which can high make sure the UPS reliability and system safety  under critical status.

◆ Large Color Dot-matrix LCD+LED Screen with multi function and user- friendly.


4Lithium-ion UPS with Traditional UPS comparison

Take 6KVA UPS with 120mins backup time as an example

No.

Item

Lithium-ion UPS

(LiFePO4)

Traditional UPS

VRLASealed Lead Acid Maintenance free

1

6KVA @120mins backup 

 1Integrated overall structure

 26KVA Lithium-ion UPS(19inch RM type): 

1pc

 3)192V/50Ah Lithium-ion pack:1pc

 4)19inch telecom RackW600mm×D800mm ×H760mm/15U):1pc

 1Split strucure

 26KVA UPSTower):1pc

 3)12V/100Ah VRLA battery:16pcs

 4battery cabinetW470mm×D760mm×H1100mm):1pc

2

Backup time @full IT Load (mins)

120

120

3

Deep cycletimes

Life timeYear

Over 2300 timeslife time 5-8years

300timeslife time 3years

4

Working Temp℃)

0-60used normally under high temperature, no need to  worry  thermal failure

0-30above 30℃ will meet thermal failure problem, shorten battery life

5

BMS 

With High efficiency and high reliable BMS (battery management system)easily control, monitor and manager each battery cell

Without Battery management system need to buy separately with high cost

6

Local Monitor

LCD+LED screen could monitor all the UPS and  Lithium0ion battery status

LCD+LED screen could monitor the UPS and  VRLA battery status.

7

Remote Monitor

RU650 Card could monitor all the UPS and Battery status (Local/ Remote monitor). The data can be transferred to the host computer in real time,  the operating data could obtain from any PC on the network also. This Two-way will greatly reduces the manpower and cost in after-sale service. 

RU620 Card could monitor all the UPS status (Local/ Remote monitor). The data can be transferred to the host computer in real time,  the operating data could obtain from any PC on the network also. This Two-way will greatly reduces the manpower and cost in after-sale service.

8

Floor spacesqm

0.48

0.54

9

Load  bearing(Kg)

132

516

10

Environment influence

Environment friendly

Acid leakage will have bad influence to environment

11

WarrantyYear

4-5 years

3 years

12

Installation time

10-15mins ,Integrated structure, Shorten installation time

120mins, split structure design, engineers  need to connect 16pcs batteries, finish UPS installation and battery pack configuration.

13

Cost

initial cost is 20% higher, while the total lifecycle cost is Low

initial cost is lower, but the total lifecycle cost is High



5.Rich Optional Accessories

BH-N Series can use SNMP Network Adapter, RS485/Dry Contact, CAN, USB port to build up a remote control and monitoring system.

 

6. Application Type

BH-N Series is designed for small important equipment/application systems, such as small financial equipment and data center, critical medical equipment and telecomm equipment.











Model

BH10N-48

BH20N-48

BH30N-48

BH10N-38.4

BH30N-96

BH60N-192

BH100N-192

Capacity

1KVA/0.8KW

2KVA/1.6KW

3KVA/2.4KW

1KVA/1KW

3KVA/3KW

6KVA/6KW

10KVA/10KW

Host Machine Specification

UPS Structure

Online Double Conversion

Appearance

Rack mount structure design

Overall Efficiency

> 90% (98% under ECO mode)

> 95% (98.5% under ECO mode)

NoiseIn 2 meters

< 50dB

Working Temp

-20-50

Storage Temp

-25-60℃(without batteries

Humidity

< 95% Non-Condensing

Safety Standard

GB/T 7260, GB/T 4943, YD/T1095, TLC

Safety Standard

EN/IEC 61000, EN/IEC 62040,

Protection

Overload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low

 

ECO mode

/

Available (Standard version does not have)

EPO mode

/

Available (Standard version does not have)

DC start

Available 

Generator compatibility

Available 

Display

LCD Display: Multi-Language with all kinds of messages. Input/ Output /bypass Status, ECO Mode , charging status, load status, Rectifier status,  INV. Temp,

 

Colored LCD screenWorking (days)SNCalendartimeUPS model & structureVersion No.history log recordshistory fault recordslanguage setECO set; time & calendar setbattery test & so on.

LED Indicators: UPS States Indicator

Sound and light alarm

Auto / Manual

Mute

Auto

Cabinet Standard

IP20

 Cooling System

Speed control fan air cooling  1000M No volume reduction

Altitude

>1000M deratethe highest is 4500M,refer to IEC62040

Input Specification

Input Voltage

220Vac208/220/230/240Vac Optional

Input Voltage Range

110~300Vac,

110~176Vac/280~300Vac limit

Input Frequency Range

44~56Hz or 54Hz~66Hz,±10Hz(Can be set)

Input power factor (PF)

0.99

THDI

≤ 3% linear load,≤ 5% Non-linear load (PF=0.8)

≤ 4linear load,≤ 6Non-linear load 

Output Specification

Output Voltage

220Vac208/220/230/240Vac Optional

Output PF

0.8

1.0  

Output Voltage Regulation

220Vac±1%Static Load);220Vac±2%50-0% Sudden Change);220Vac±5%100-0% Sudden Change

Output Freq(utility

46Hz≤input Freq.≤54Hzoutput Freq.=input Freq.

When Input Freq.<46Hz or >54Hz, the Output Freq will be Locked at 50Hz

Output Freq(Battery

50Hz±0.1%

 

Output Wave form

Pure sine wave

 

Distortion

<1%Linear Full Load),3%100%  Non-Linear Full Load

<2%Linear Full Load),5%100%  Non-Linear Full Load

Overload


102%~110% load 30mins

110%~125% load 10mins

125%~150% load 500ms

 

102%~110% load 30mins Bypass

110%~130% load 10mins Bypass

130%~150% load 30s Bypass

150% 500ms Bypass

97% Buzzer alarm released,

70% Auto resume inverter

Crest Ratio

31

Inverter efficiency

 90%

 95%

Short circuit

Circuit Auto ProtectionOutput Voltage/Current 0

Output Abnormal

INV. Output Auto-Locked Protection

Noise Suppression

EMI/RFI Wave Filter

Battery voltage low

Shut down protection

Dynamic Response

3% at full load, recovering in 20ms

Auto restart function

available

Software set on/off

available

Bypass Specification

Static Bypass Transfer Time

0ms

Static Bypass Range

80Vac±5%285Vac±5%

Bypass -> INV Transfer Time

< 2ms

Communication Specification

UPS Communication Port

Default RS232SNMP/RS485/dry contactoptional

Lithium-ion pack Communication Port

Default CAN/485 

Monitoring software

Multi-functional Monitoring System, power and battery status,power failure,low battery voltage,remote shutdown, control menu

Lithium-ion Battery Specification

Type

LiFePO4

Nominal voltage/Number of cells

48Vdc/15-16s

48Vdc/15-16s

48Vdc/15-16s

38.4Vdc/12s

96Vdc/30s

192Vdc/60s

192Vdc/60s

Equalizing charge voltage

54.0-56.5Vdc

54.0-56.5Vdc

54.0-56.5Vdc

43.2Vdc

108Vdc

216Vdc

216Vdc

Charging current

MAX.5A

MAX.5A

MAX.5A

MAX.12A

MAX.12A

MAX.12A

MAX.12A

25Ah Full load standby time(min)

50

40

30

55

60

60

40

50Ah Full load standby time(min)

100

80

60

/

120

120

60

100Ah Full load standby time(min)

200

160

120

/

/

220

150

Physical Parameters

UPS Size MM(DxWxH)

320×440×88/2U 

450×440×88/2U 

450×440×88/2U 

400×440×88/2U 

400×440×88/2U 

470×440×88/2U 

470×440×88/2U 

Net Wight(Kg)

7.5

10.0

14.0

5.5

8.0

10.0

10.5

25Ah Lithium battery pack size (MM)

400×440×88/2U

400×440×88/2U

400×440×88/2U

400×440×88/2U

450×440×175/4U

480×440×220/5U

480×440×220/5U

50Ah Lithium battery pack size (MM)

400×440×132/3U

400×440×132/3U

400×440×132/3U

/

500×440×220/5U

500×440×220/5U

480×440×160

500×440×220/5U

480×440×160

100Ah Lithium battery pack size (MM)

500×440×132/3U

550×440×132/3U

550×440×132/3U

/

500×440×220/5U

480×440×160

400×440×132/3U

(600×440×220/5U)x2

400×440×132/3U

(600×440×220/5U)x2

25Ah Lithium battery pack net weight (Kg)

20.0

20.0

20.0

19.0

30.0

60.0

60.0

50Ah Lithium battery pack net weight(Kg)

35.0

35.0

35.0

/

55.0

110.0

110.0

100Ah Lithium battery pack net weight(Kg)

55.0

55.0

55.0

/

 

110.0

 

     230.0

 